PURPOSE:
To verify that the airflow direction between areas with pressure difference are acceptable.
PROCEDURE:- This test should be performed by trained or certified personnel.
- Implementation ISO 14644-3:2005 standards.
- All results are to be recorded on video or photograph.
- Ensure all doors in the room serving by HVAC System tag no. AHU are closed.
- Using a suitable smoke stick/pencil, apply smoke to the higher pressure side and observe the direction of flow of smoke.
- Record the details of all test equipment used in Appendix.
ACCEPTANCE CRITERIA:
The direction of airflow indicated by smoke is from higher pressure to lower pressure.